Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T06FR02855
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | The gate blocking the FDC's has been removed providing immediate access. | |
12/28/2006 | VIOL - FIRE PROTECTION SYSTEMS | Continued | Met with Janet Synder (4 D properties). Explained what areas of the fence needed removed. | |
12/08/2006 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 912.3 Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimum of 3 feet (914 mm). -East side FDC's need to be accessible |