Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Case: T06FR02854

Parcel: 137105050


Addresses:

5550 S 12TH AV #156

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
02/12/2007 VIOL - MEANS OF EGRESS Approved all violations have been corrected.
12/29/2006 VIOL - MEANS OF EGRESS Compliance signs are lit
12/29/2006 VIOL - MEANS OF EGRESS Violation combustables piled in path of exit door swing.
12/29/2006 VIOL - MEANS OF EGRESS Compliance slide bolt lock is removed
12/29/2006 VIOL - MEANS OF EGRESS Compliance replaced double key locking cylinder with thumb bolt latch.
12/13/2006 VIOL - MEANS OF EGRESS Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or
surface bolts are not permitted. Remove surface bolt on rear interior exit door.
12/13/2006 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge or effort. Replace double key locking cylinder with a manually operated thumb latch bolt on egress side of rear exit door.
12/12/2006 VIOL - MEANS OF EGRESS Violation 1011.2 Illumination. Exit signs shall be internally or externally
illuminated. Replace batteries in exit signs
12/12/2006 VIOL - MEANS OF EGRESS Violation 1004.3 Posting of occupant load. Every room or space that is
an assembly occupancy shall have the occupant load of the
room or space posted in a conspicuous place. You will be referred to DSD for Certificate of Occupancy.
12/12/2006 VIOL - MEANS OF EGRESS Violation 1027.3 Obstructions. A means of egress shall be free from obstructions. Remove accumulated items and garbage can blocking rear exit doors and maintain the required width.