Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR02854
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | all violations have been corrected and hazards abated. | |
| 12/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | towel removed | |
| 12/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | covers provided for open outlets in storage and wax rooms | |
| 12/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Need cover for circuit breaker box | |
| 12/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | remove extension cord from under counter. | |
| 12/13/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Provide an approved cover for the circuit breaker box in rear storage area. |
|
| 12/12/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cover-ings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. |
|
| 12/12/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Remove items blocking access to electrical panel. |
|
| 12/12/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 603.5.1 Guard against contact. The heating element or combustion chamber shall be permanently guarded so as to prevent accidental contact by persons or material. Remove towel under wax heater or unplug when not in use. |
|
| 12/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Replace outlet covers in Waxing Room (2) and S wall of storage room. |