Case: T06FR02790

Parcel: 105095520


Addresses:

4888 N STONE AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR02790

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2006 INSP - FULL Approved approved
11/29/2006 INSP - FULL Violation 1). Sprinkler inspection and report due. Current report indicates flow switch repair needed. This repair shall be completed. IFC 901.6
2). Emergency lighting out of service on 2nd floor. IFC 1026.5
3). All smoke detectors shall be tested and report submitted. IFC 901.6
4). Move manual hood activation from obstruction in kitchen IFC 901.6