Case: T06FR02789

Parcel: 12401002B


Addresses:

1339 E 1ST ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
12/14/2006 INSP - FULL Approved approved
11/28/2006 INSP - FULL Violation 1). Fire sprinkler test and inspection shall be submitted and all required repairs shall be completed. IFC 901.6
2). Fire alarm test report shall be submitted. IFC 901.6 Smoke detectors shall be tested
3). Mount all fire extinguishers. IFC 906.7
4). Clan all lint from ceiling in laundry room. IFC 304.1
5). 24" aisle shall be required in basement luggage area. IFC 1027
6). Emergency power light out on 2nd floor. IFC 1026
7). REMOVE COVER ON EXIT LIGHT. IFC 1026.3