Case: T06FR02786

Parcel: 137051130


Addresses:

501 W IRVINGTON RD


Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T06FR02786

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2006 INSP - AST/UST Approved ESO has been changed so that it cannot be reset at the button, must be manually reset at the electrical panel. Passed.
12/14/2006 INSP - AST/UST Correction Required Final not ready due to ESO can be reset at switch. All other checks are OK, will need to call in for another inspection.
12/07/2006 INSP - AST/UST Approved Secondary piping inspection passed.
12/05/2006 INSP - AST/UST Approved Primary piping inspection and vapor recovery line passed.
11/28/2006 INSP - AST/UST Continued met with Will Hunter to look at current E-stop location. I will be requiring them to add a second location to the north of the dispensers.