Case: T06FR02785

Parcel: 12901045A


Addresses:

1900 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T06FR02785

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2007 INSP - AST/UST Approved Final inspection passed
12/27/2006 INSP - AST/UST Compliance Primary and secondary piping passed. Dispenser sumps passes leak test.
12/22/2006 INSP - AST/UST Correction Required Piping inspection failed, secondary guages were inop. Vent pipes failed bubble test. Primary pipe passed.
12/21/2006 INSP - AST/UST Correction Required Piping inspection failed, secondary will not hold pressure. Informed Dan of placement for bollards.
11/28/2006 INSP - AST/UST Continued inspected excavation, fabric in place, 12" bed of pea gravel down prior to tanks being set (2 x 20000 gal). Tanks arrived on vacuum, will check after backfilled.
11/21/2006 INSP - AST/UST Continued met with Marty Wildman (A & H Contracting Services), Dan Froyland (Triumph Builders) to discuss project. Tanks to be set on the 28th at 0800 hrs.