Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR02775
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2006 | INSP - FULL | Approved | Final inspection. | |
| 11/21/2006 | INSP - FULL | Violation | 2003 IFC-901.6 The fire extinguishers shall be serviced annually. 2003 IFC-1017.2.2 Emergency back up lights and exit lights shall be in good working condition at all times. 2003 IFC-605 The electrical room shall not be used as a storage room. 2003 IFC-605.5 Extension cords shall not be used as permanent wiring. Remove or replace with power surge protectors, traning room. 2003 IFC-703.1 Ceiling tile missing, shall replace to keep the fire rating. 2003 IFC-315.2 Combustables shall be storaged neat and orderly. 2003 IFC-Compress gas cylinder shall be secured to prevent accidents. |