Case: T06FR02770

Parcel: 12109290B


Addresses:

2221 N ROSEMONT BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR02770

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2007 INSP - FULL Approved approved
11/21/2006 INSP - FULL Violation 1). Tree is obstructing address. IFC 505
2). Repair self-closing door, 1st floor hallway. IFC 703.2.2
3). Repair electrical light fixture at apt 122
4). Currently 3000 square foot office/business area has fire sprinkler that has been disconnected.
This must be repaired or removed. To remove an appeal must be sent Deputy Chief Uthe
IFC 901.6 states:
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.