Case: T06FR02767

Parcel: 12412293A


Addresses:

301 S PARK AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR02767

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2006 INSP - FULL Approved
11/20/2006 INSP - FULL Violation 1). Fire sprinkler test and inspection report must be sent by 11-28-06.
IFC 903.1
2). All required repairs on report shall be completed by 12-1-06
3). System must be monitored as per IFC 903.4.1, which states:

903.4.1 Signals. Alarm, supervisory and trouble signals
shall be distinctly different and shall be automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72 or, when approved by the fire code official, shall sound an audible signal at a constantly attended location.
Exceptions:
1. Underground key or hub valves in roadway boxes
provided by the municipality or public utility are
not required to be monitored.
2. Backflow prevention device test valves, located in
limited area sprinkler system supply piping, shall
be locked in the open position. In occupancies required
to be equipped with a fire alarm system, the
backflow preventer valves shall be electrically supervised
by a tamper switch installed in accordance
with NFPA 72 and separately annunciated.


Currently this signal is not constantly being attended.
This shall be corrected by 12-1-06


Currently the outside water flow is not functioning. This shall be repaired by 12-1-06.


903.4.2 Alarms. Approved audible devices shall be connected
to every automatic sprinkler system. Such sprinkler
water-flow alarm devices shall be activated by water flow
equivalent to the flow of a single sprinkler of the smallest orifice
size installed in the system. Alarm devices shall be provided
on the exterior of the building in an approved location.
Where a fire alarm system is installed, actuation of the automatic
sprinkler system shall actuate the building fire alarm
system.