Inspection Status: Approved
Inspection History: INSP - AST/UST
| Date |
Description |
Inspector |
Results |
Comments |
| 11/22/2006 |
INSP - AST/UST |
|
Approved |
Final inspection passed, tested emergency shut-offs, OK to open. |
| 11/16/2006 |
INSP - AST/UST |
|
Approved |
secondary piping inspection passed. |
| 11/14/2006 |
INSP - AST/UST |
|
Correction Required |
FAILED- secondary piping inspection, diesel unable to hold pressure, sump boxes leaking |
| 11/09/2006 |
INSP - AST/UST |
|
Approved |
Primary piping inspection for 8 new dispensers and piping under canopy. Curbs are less than 6" so bollards will need to be provided. Contractor to submit drawing. Drop tube overfill float broken and shall be replaced prior to placing in service. |