Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2006 | INSP - FULL | Approved | approved | |
| 11/08/2006 | INSP - FULL | Violation | 1). Retest all smoke detectors in each room repairs if need and submit log indicating testing and repairs. IFC 906.1 2). Address is obstructed. Trim tree. IFC 505.1 3). Exit sign on 1st floor shall be repaired. IFC 1026.3 4). Currently lock in which it is difficult to cut off is on electrical access. This lock shall be removed and replaced with locking that can be cut off easily. IFC 605.1 5). Replace ceiling tiles in Rec. room. IFC 703.1 6). Currently trouble light is showing on fire alarm. REPAIR fire alarm immediately. IFC 901.6 7). Full test of fire alarm shall be conducted. IFC 901.6 8). Remove all debris from stairs. IFC 1027.3 9). Full fire sprinkler test and inspection report shall be submitted. IFC 901.6 10). Add smoke detector to new sleeping area. |