Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR02698
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 605.1- Identified electrical hazards shall be abated. 1. light fixture in safe room shall be covered. 2. wires shall be protected below the ceiling and shall not extend through ceiling. (x 3) 3. motors over food service shall be covered. 4. motor under drink fountain shall be shielded from combustibles. 5. switch in water heater closet shall be replaced and covered. 6. cord to coffee machine shall be repaired. |
|
10/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 605.4- Multiplug adapters and unfused plug strips shall be prohibited. (N Wall) |