Case: T06FR02684

Parcel: 13205015N

Inspection Status: Approved

Inspection History: INSP - AST/UST

Date Description Inspector Results Comments
11/13/2006 INSP - AST/UST Approved PASSED- met w/Richard Lee of Fed EX, flowed diesel and tested E-stop, removed bag from fire extinguisher. Ready for use. Permit faxed to Dave Frye.
11/09/2006 INSP - AST/UST Correction Required Emergency stop needs to be on manual reset. Linkage on sheer valve is broken.
11/08/2006 INSP - AST/UST Partial Approval Appeal approved by fire marshal, contractor and owner notified. Need final inspection before putting in service.
10/18/2006 INSP - AST/UST Correction Required Not Ready for final. No fire extinguisher, needs to appeal the dispenser distancefrom building. Form was sent to contractor.