Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Case: T06FR02663

Parcel: 11507315B


Addresses:

25 E DRACHMAN ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
12/22/2006 VIOL - FIRE PROTECTION SYSTEMS Approved appeal approved fron removal of smoke detectors
11/14/2006 VIOL - FIRE PROTECTION SYSTEMS Violation 1). Fire alarm test reports shows that smoke detectors did not activate alarm on panel. These smoke detectors may or may not be required in warehouse. IFC 901.6 states the following:

901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.

Permission must be granted from Tucson Fire Department before removal or repaired.