Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T06FR02646

Parcel: 10607010A


Addresses:

1109 W PRINCE RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR02646

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2006 INSP - FULL Approved approved
10/04/2006 INSP - FULL Violation 1). Currently on front door, opening device is to high. This is in violation of IFC 1008.1.8.2 which states:

1008.1.8.2 Hardware height. Door handles, pulls, latches, locks and other operating devices shall be installed 34 inches (864 mm) minimum and 48 inches (1219 mm) maximum above the finished floor.
Locks used only for security purposes and not used for normal
operation are permitted at any height.

Lower opening to device to above specifications.

2). Fire alarm shall be tested and report submitted to TFD IFC 901.6

3). Test all smoke detectors and submit given smoke detector log. IFC 901.6

4). Smoke detector in break room needs cleaning and repair. IFC 901.6