Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR02646
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2006 | INSP - FULL | Approved | approved | |
10/04/2006 | INSP - FULL | Violation | 1). Currently on front door, opening device is to high. This is in violation of IFC 1008.1.8.2 which states: 1008.1.8.2 Hardware height. Door handles, pulls, latches, locks and other operating devices shall be installed 34 inches (864 mm) minimum and 48 inches (1219 mm) maximum above the finished floor. Locks used only for security purposes and not used for normal operation are permitted at any height. Lower opening to device to above specifications. 2). Fire alarm shall be tested and report submitted to TFD IFC 901.6 3). Test all smoke detectors and submit given smoke detector log. IFC 901.6 4). Smoke detector in break room needs cleaning and repair. IFC 901.6 |