Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR02578
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2006 | INSP - FULL | Approved | Knox box installed. | |
09/14/2006 | INSP - FULL | Violation | 2003 IBC- 110 The Cof O shall be posted. 2003 IFC-703.1 Tiles missing from ceiling and two holes in ceiling shall repair. This is for the fire resistive construction. 2003 IFC-610.1 Hood system shall be serviced annually. 2003 IFC-605.5 Extension cords shall not be a substitute for permanent wiring. 2003 IFC-598.5 The sprinkler control room door shall be labeled fire sprinkler controls. A knox box shall be installed for quicker access. |