Case: T06FR02569

Parcel: 13314227C


Addresses:

1400 N WILMOT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR02569

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2006 INSP - FULL Approved APPROVED
09/13/2006 INSP - FULL Violation 1). 2006 fire sprinkler test shall be submitted to TFD, and all repairs shall be completed by 10-11-06. IFC 901.6
2). Fire alarm test shall have all smoke detectors addressed on fire alarm report, including duct smoke detectors. Magnetic door closures shall also be addressed. TFC 901.6