Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2006 | INSP - FULL | Approved | Final inspection. | |
| 09/12/2006 | INSP - FULL | Violation | 20003 IFC-1008.1.2 Emergency exit lights shall be illuminated at all times. 2003 IFC-906.9 Fire extinguisher shall be serviced annually and shall have a current sevice tag attached.This is for the weilding area. 2003 IFC-3404.3 A flammable liquid cabinet is required for the two 47.2 L propane drums. Two forklifts operate on propane. 2003 UFC- 110 The Cof O is required shall be posted next to the business license. |