Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR02548
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2006 | INSP - FULL | Approved | all approved | |
09/11/2006 | INSP - FULL | Violation | 1). Current fire sprinkler test shall be submitted and all repairs shall be completed. IFC 901.6 Test report shall be on premises. 2). Smoke detectors along with entire fire alarm system shall be tested and report submitted. Smoke detectors shall b addressed on report. IFC 901.6 3). Log shall be required on emergency generator test and all work completed. IFC 604.3.2 4). All construction on 2nd floor partitions over 5' 9" are subject to permit and follow-up inspections. 2003 IBC 110. Current construction shall be referred to City of Tucson DNR. 5). All combustible material shall be removed from interior stairwell. IFC 1027.3 |