Inspection Status: Violation
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/09/2006 |
VIOL - PRECAUTION AGAINST FIRE |
|
Violation |
IFC 303.4- Asphalt kettles shall be attended at all times. The employee shall be within 100 ft of the kettle and in line of sight. Ladders shall not form a part of the route between the kettle and the attendant. |
| 08/09/2006 |
VIOL - PRECAUTION AGAINST FIRE |
|
Violation |
IFC 303.5- There shall be a portable fire extinguisher within 25 ft of the asphalt kettle and one on the roof. They shall be a minimum of 40B:C. |