Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T06FR02409
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2006 | INSP - FULL | Violation | Building 2010 had the same violations as 2104 suite 103. In the engineering support crib room has storage of CO2, CO, and NO cylinders. this room will need mechanical ventalation, explosive proof wiring.the exhaust motors will also have to be explosive proof. 1 hr fire rate door from office to lab. emergency back up lights are needed in the large office area if power failure,this will light the way out. The hallways will need exit signs to show the way out, from one room to another room to help people out in an emergency. |