Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2006 | VIOL - MEANS OF EGRESS | Approved | ||
| 08/08/2006 | VIOL - MEANS OF EGRESS | Violation | Bolt lock: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ***Remove bolt lock. |
|
| 08/08/2006 | VIOL - MEANS OF EGRESS | Violation | Double keyed back door: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ***Remove double keyed lock and replace with a "Blank". ***Existing doorknob lock OK, or replace it with a "thumb turn" bolt. [Only 1 lock permitted on each door, no keyed locks] |
|
| 08/08/2006 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: TFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. ***Repair emergency lights [x2]. |
|
| 08/08/2006 | VIOL - MEANS OF EGRESS | Violation | Exit signs not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. ***Fix light in exit signs. |
|
| 08/08/2006 | VIOL - MEANS OF EGRESS | Violation | Patio exit: 1008.1 Doors. Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1017.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. Means of egress doors shall be readily distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Mirrors or similar reflecting materials shall not be used on means of egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials. ***Create and exit from the patio, easily opened, and clearly marked with an exit sign. Check with building codes for approved configuration. |