| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2006 | INSP - FULL | Approved | ||
| 07/27/2006 | INSP - FULL | Violation | 1). Fire alarm test shall be submitted to TFD and all required corrections shall be completed. IFC 901.6. Heat detectors must be addressed on fire alarm report. 2). Currently there is combustible storage in the same room as a gas feed hot water heater. The fire code states: 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. All combustible storage must be removed. 3). Egress Illumination lights did not work when tested. Shall be repaired is necessary in the following areas; fellowship Hall, #2 Kitchen. IFC 1026.5 |