Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T06FR02293
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2006 | VIOL - MEANS OF EGRESS | Approved | TFC 1027.2 Exiting / exit access PRE-CITATION: Three required exterior exits are routinly being kept locked.Corrections were made in the presence of the fire offical. Order was given to keep these doors unlocked during business hours . Failure to do so will result with a citation being issued. Exit access in hallway where beer kegs are stored is obstructed by the storage of beer kegs. |
|
07/26/2006 | VIOL - MEANS OF EGRESS | Approved | TFC 1008.1.8 Door Operations, All exterior exits shall be provided with a thumb-turn lock with the exception of the main enterance door. |
|
07/26/2006 | VIOL - MEANS OF EGRESS | Approved | TFC 1008.1.8.3 Signage: A sign shall be posted ajasent to the doors provided with thumb-turn locks that states: " THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED " |
|
07/26/2006 | VIOL - MEANS OF EGRESS | Approved | TFC 1008.1.9 Panic Hardware: The wrought iron screen door located at the bottom of the stairs leading to the parking lot from the 2nd. floor shall be provided with panic hardware. |