Case: T06FR02293

Parcel: 11520262A


Addresses:

2075 W GRANT RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T06FR02293

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2006 VIOL - MEANS OF EGRESS Approved TFC 1027.2 Exiting / exit access

PRE-CITATION:
Three required exterior exits are routinly being kept locked.Corrections were made in the presence of the fire offical. Order was given to keep these doors unlocked during business hours . Failure to do so will result with a citation being issued.

Exit access in hallway where beer kegs are stored is obstructed by the storage of beer kegs.
07/26/2006 VIOL - MEANS OF EGRESS Approved TFC 1008.1.8 Door Operations,
All exterior exits shall be provided with a thumb-turn lock with the exception of the main enterance door.
07/26/2006 VIOL - MEANS OF EGRESS Approved TFC 1008.1.8.3 Signage: A sign shall be posted ajasent to the doors provided with thumb-turn locks that states:
" THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED "
07/26/2006 VIOL - MEANS OF EGRESS Approved TFC 1008.1.9 Panic Hardware:

The wrought iron screen door located at the bottom of the stairs leading to the parking lot from the 2nd. floor shall be provided with panic hardware.