Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR02293
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | TFC 605.5 Misuse of extension / flex cords in the following locations. 1.) dining room area, SW corner, ext. cord. 2.) " , cord extending through wall. 3.) " , cord supplying power to TV sets on tables is extended under floor covering and through wall. 4.) dining area north end, same violation as on # 3 with 5 tables . 5.) conference room, ext. cord to TV set. 6.) dry storage room, cord through ceiling x 2. 7.) kitchen area west wall next to deep vat fryer, ext. cord. 8.) top side of soffet over main bar area,ext. cords. |
|
07/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | TFC 605.6 Electrical ,Open junction boxes in the following locations; 1.) conference room, under counter, cover plate. 2.) main office, at enterance and under counter, cover plates. 3.) top side of soffet, open junction boxes. 4.) wall next to fusball table, cover plate. 5.) 2nd. floor next to exit door, open juntion box with exposed wiring. |
|
07/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | TFC 605.4 Misuse of unapproved multiple adapters in following areas. 1.) in main dining room, under neon sign. 2.) office, under counter. 3.) kitchen, west wall, next to deep vat fryer x 2. |