Case: T06FR02265

Parcel: 107031540


Addresses:

2450 N HUACHUCA DR

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/16/2006 INSP - FULL Approved approved
07/20/2006 INSP - FULL Violation 1). Fire alarm test report shall be submitted to TFD, and all corrections shall be completed. IFC 901.6
2). Smoke detectors not on report shall be tested and log submitted. IFC 901.6
3). Egress Illumination lights shall be tested in each room ,and written documentation shall be submitted showing testing. IFC 901.6