Case: T06FR02253

Parcel: 114540650

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
08/18/2006 VIOL - MEANS OF EGRESS Approved
07/19/2006 VIOL - MEANS OF EGRESS Violation Exit sign not lit:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.
***Fix light in exit signs. [South, and Kitchen]
07/19/2006 VIOL - MEANS OF EGRESS Violation TFC 1027.6 [ammendment] Panic Hardware:
Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.
***Remove and "plug" both deadbolt locks on doors [S. side] with existing panic hardware.
07/19/2006 VIOL - MEANS OF EGRESS Violation Blocked exit:
1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
***Clear exit area, and maintain it this way.
07/19/2006 VIOL - MEANS OF EGRESS Violation Main entry:
TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background.
*** Place above-mentioned sign on or near front door in an approved manner.