Case: T06FR02013

Parcel: 13312006J

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T06FR02013

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2006 VIOL - MEANS OF EGRESS Approved
06/15/2006 VIOL - MEANS OF EGRESS Violation 2nd Exit [E side dining room]:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
***Change to "thumb latch" bolt on E door.
06/15/2006 VIOL - MEANS OF EGRESS Violation Main entry:
TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background.
*** Place above-mentioned sign on or near front door[s] in an approved manner.