Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR02013
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | only 1 extension cord left to replace. all else abated in this field | |
06/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ***Clear area in front of electrical panel in an approved manner. |
|
06/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Multiplug adapters: TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ***Remove noncomplying devices. |
|
06/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. *** Replace with approved power strip. ***Remove from going thru ceiling. [kitchen and office] |
|
06/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Open spaces in electrical box: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ***Place "blanks" in open spaces. Re-inspection scheduled for July 3rd, 2006. |