Case: T06FR02013

Parcel: 13312006J

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR02013

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2006 VIOL - BUILDING SVCS & SYSTEMS Approved only 1 extension cord left to replace. all else abated in this field
06/15/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:
TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
***Clear area in front of electrical panel in an approved manner.
06/15/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:
TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
***Remove noncomplying devices.
06/15/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
*** Replace with approved power strip.
***Remove from going thru ceiling.
[kitchen and office]
06/15/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Open spaces in electrical box:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
***Place "blanks" in open spaces.


Re-inspection scheduled for July 3rd, 2006.