Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T06FR01993

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2006 VIOL - PRECAUTION AGAINST FIRE Approved Re-inspected 6/15/06. All abated! Good Job.
06/15/2006 VIOL - PRECAUTION AGAINST FIRE Violation Clearance below sprinklers:
TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
***Remove storage to 18 inches or more below sprinkler head.

Notes:
C of O on site.
Hood system and extinguishers are current.