Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2006 | INSP - FULL | Approved | C of O needed | |
| 06/07/2006 | INSP - FULL | Violation | 1). Currently no address can be found on building. Address must be affixed to building as per Pima County Address display requirements. IFC 505.1 Handout given. 2). Fire alarm test and inspection report due. Last report dated 5/05 IFC 901.6 3). Remove wires from fire alarm piping. IFC 901.6 4). Replace portable fire extinguisher from Young toddler room. IFC 901.6 5). Electrical lights shall be repaired in the exterior. IFC 605.1 6). Certificate of Occupancy is required for this educational building. As per IBC 110.1 which states; 110.1 Use and occupancy. No building or structure shall be used or occupied, and no change in the existing occupancy classification of a building or structure or portion thereof shall be made until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. This may be found in records at 201 N Stone. |