Case: T06FR01793

Parcel: 106040570


Addresses:

321 E YAVAPAI RD

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
07/18/2006 VIOL - PRECAUTION AGAINST FIRE Approved all approved. Thank you
06/06/2006 VIOL - PRECAUTION AGAINST FIRE Violation 1). Certificate of Occupancy is required as per IBC 1101.1, which states:

CERTIFICATE OF OCCUPANCY
110.1 Use and occupancy. No building or structure shall be used or occupied, and no change in the existing occupancy classification of a building or structure or portion thereof shall be made until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction.

This shall be referred to City of Tucson Department of Neighborhood Services if C of O cannot be produced.
2). Fire alarm shall be tested and report submitted to TFD. IFC 901.6
3). Repair hardware on door in after schoolroom. IFC 1027.2
4). Remove paint from 1-year-old hallway smoke detector. IFC 901.6. If decision to remove, written permission must be granted to remove.