Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2006 | VIOL - PRECAUTION AGAINST FIRE | Approved | all approved. Thank you | |
| 06/06/2006 | VIOL - PRECAUTION AGAINST FIRE | Violation | 1). Certificate of Occupancy is required as per IBC 1101.1, which states: CERTIFICATE OF OCCUPANCY 110.1 Use and occupancy. No building or structure shall be used or occupied, and no change in the existing occupancy classification of a building or structure or portion thereof shall be made until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. This shall be referred to City of Tucson Department of Neighborhood Services if C of O cannot be produced. 2). Fire alarm shall be tested and report submitted to TFD. IFC 901.6 3). Repair hardware on door in after schoolroom. IFC 1027.2 4). Remove paint from 1-year-old hallway smoke detector. IFC 901.6. If decision to remove, written permission must be granted to remove. |