Case: T06FR01785

Parcel: 130140260


Addresses:

4112 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/07/2006 INSP - FULL Approved final and referred Cof O.
06/16/2006 INSP - FULL Correction Required need more time.
06/06/2006 INSP - FULL Correction Required 2003 IFC-605.6 Broken outlet behind the Flintstone ride. need the metal cover plate.
2003 IFC-605.5 Extension cord behind team rush machine, broken outlet on the south wall,need metal cover plate.
2003 IFC-9801.6.8 Sprinkler head caller down on top of sprinkler covering the head,above Police Trainer.other above the carryout sign.2003 IFC-703.1 Fire Riser room tile missing along the piping chase, need to cover up the holes.
2003 IFC-30033.3.3 Compress gas cylinders,secure to prevent accidents.
2003 IFC-703.1 Employees room shall repair hole in north wall.
2003 IFC-105.3 Shall post ther Cof O.
2003IFC-605.5 Extension cord and flexible cords shall not be affixed to structures, extended through ceilings, "Gift shop area."