Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR01785
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2006 | INSP - FULL | Approved | final and referred Cof O. | |
06/16/2006 | INSP - FULL | Correction Required | need more time. | |
06/06/2006 | INSP - FULL | Correction Required | 2003 IFC-605.6 Broken outlet behind the Flintstone ride. need the metal cover plate. 2003 IFC-605.5 Extension cord behind team rush machine, broken outlet on the south wall,need metal cover plate. 2003 IFC-9801.6.8 Sprinkler head caller down on top of sprinkler covering the head,above Police Trainer.other above the carryout sign.2003 IFC-703.1 Fire Riser room tile missing along the piping chase, need to cover up the holes. 2003 IFC-30033.3.3 Compress gas cylinders,secure to prevent accidents. 2003 IFC-703.1 Employees room shall repair hole in north wall. 2003 IFC-105.3 Shall post ther Cof O. 2003IFC-605.5 Extension cord and flexible cords shall not be affixed to structures, extended through ceilings, "Gift shop area." |