Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T06FR01737
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 12/13/2006 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Sprinkler test for the entire building is approved, however the heads are blocked in the East suite, rendering the system out of service. ***See note below. |
|
| 06/05/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Maintain sprinkler system [cannot be above ceiling]: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. *** All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code. Please document the adequate coverage of the system by an approved fire service company. Note: 901.6.2 Records. Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. |