Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE RESIST.RATED CONST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2006 | VIOL - FIRE RESIST.RATED CONST | Approved | All abated in this catagoty. | |
| 06/05/2006 | VIOL - FIRE RESIST.RATED CONST | Violation | Missing or moved ceiling tiles: TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles. |