Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR01737

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2006 VIOL - BUILDING SVCS & SYSTEMS Approved All Abated in this catagory.
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:
TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
***Clear area in front of electrical panel in an approved manner.
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Lights with straw decoration:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
***unplug lights with straw decoration.
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire boxes/ splices:
TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
***Cover wires in an approved manner with face plate.
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Cords thru ceiling & other extension cords:
Extension cords:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
*** [cords not going thru ceiling] replace with approved power strip.
*** Remove cords passing thru ceiling.