Case: T06FR01688

Parcel: 11451137D

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR01688

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2006 VIOL - FIRE PROTECTION SYSTEMS Approved
05/31/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguisher on floor:
TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.
TFC 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).
***Mount extinguisher on wall in an approved manner.
05/31/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Maintain sprinkler system:
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
*** All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.


Re-inspection scheduled for 6/16/06.