Case: T06FR01624

Parcel: 11451142A

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T06FR01624

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2006 VIOL - MEANS OF EGRESS Approved
08/18/2006 VIOL - MEANS OF EGRESS Partial Approval
05/30/2006 VIOL - MEANS OF EGRESS Violation Slide bolts on back door:
TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
***Remove bolts and replace with thumb turn dead bolt.
05/30/2006 VIOL - MEANS OF EGRESS Violation Exit signs, and Emergency lighting:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.
TFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
1. Repair all exit signs internal lighting.
2. Repair all emergency lighting units.