Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR01624
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 05/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ***1. Replace with approved power strip. [2 TV's, office, Salad Bar, etc.] ***2. Remove all cords passing thru ceiling. Replace with approved electrical box, installed acording to electrical code. |
|
| 05/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Splices above heating lamp: TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ***Replace entire wire in an approved manner from heat lamp [directly] to a new approved outlet. |
|
| 05/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Multiplug adapters: TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ***Remove noncomplying devices. [Toy house game, etc] |
|
| 05/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Open spaces in electrical panel: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ***1. Place "blanks" in open spaces. ***2. Remove tape from panel, disallowing breaker to "trip". ***3. Cover Electrical panel with an approved cover. ***4. Cover Fan in bathroom. |
|
| 05/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Hood system: [M] 610.1 General. Commercial kitchen exhaust hoods shall comply with the requirements of the International Mechanical Code. 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ***1. Replace all screens; maintain free from grease and buildup; clean as often as neccessary to be grease free! [cooking without screens will result in possible cease operations order [red tag] from the fire marshal.] ***2. Clear area in front of "pull station", and make sure ALL employees know what and where it is! |