Case: T06FR01502

Parcel: 140122160


Addresses:

4951 S CAMPBELL AV

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/07/2006 INSP - FULL Approved final inspectrion, referred Cof O.
05/25/2006 INSP - FULL Correction Required 2003 IFC-105.3.3 Cof O shall be posted.
2003 IFC-605.3 Open junction box next to the service window.
2003 IFC-605.5.2 Electrical panel with open switch space shall have a approved cover,to prevent sparks from falling out.
2003 IFC-605 Light bulb in the freezer shall have the cover gard.protect from the humidity in the freezer.
2003 IFC-904.11.2 Type 1 commercial hood system in the kitchen shall have a automatic fire extinguisher with the sprinkler heads covering the deep frying equipment. shall have the fusable links replaced.