Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR01502
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2006 | INSP - FULL | Approved | final inspectrion, referred Cof O. | |
05/25/2006 | INSP - FULL | Correction Required | 2003 IFC-105.3.3 Cof O shall be posted. 2003 IFC-605.3 Open junction box next to the service window. 2003 IFC-605.5.2 Electrical panel with open switch space shall have a approved cover,to prevent sparks from falling out. 2003 IFC-605 Light bulb in the freezer shall have the cover gard.protect from the humidity in the freezer. 2003 IFC-904.11.2 Type 1 commercial hood system in the kitchen shall have a automatic fire extinguisher with the sprinkler heads covering the deep frying equipment. shall have the fusable links replaced. |