Case: T06FR01493

Parcel: 107083240


Addresses:

708 W GRANT RD


Inspection Status: Approved

Inspection History: INSP - LIFE SAFETY

Case Number - T06FR01493

Inspection Description - INSP - LIFE SAFETY

Inspection Status - Approved

Date Description Inspector Results Comments
05/25/2006 INSP - LIFE SAFETY Approved TFC 605.6
Open juntion boxes shall be prohibited. Approved covers shall be provided for all switch and electrical outlets.
You shall correct the violations in the following locations:
1.) in the ceiling of the main dinning room, X 4.
2.) in the ceiling outside, front corridor.
3.) door to kitchen enterance.
4.) in kitchen passageway.
5.) in cooking area , west wall next to hood.
6.) rear room, old boxing gym, to the outside over north door.
05/25/2006 INSP - LIFE SAFETY Approved TFC 605.5
Flexible cords shall not be extended through walls, ceilings, or floors. Extention cords shall not be a substitute for permanent wiring.
You shall correct the following:
1.) wire running through the ceiling inthe room marked "Private".
2.) misuse of cord running to the top of the roof.
05/25/2006 INSP - LIFE SAFETY Approved TFC 605.1
All electrical wiring shall be installed in accordance with the NEC ( National Electric Code )