Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR01444
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2006 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | Cords have been removed. | |
05/01/2006 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | Multiplug adapters have been removed. | |
05/01/2006 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | Covers provided for outlets. | |
04/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.5 Extension dords shall not be used as a source for permanent wiring. Remove two extension cords used in the reception area. | |
04/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.4 Multiplug adapters are prohibited. Remove multiplug adapters from the reception area behind desks on N and E Walls. | |
04/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.6 Open junction boxes shall be covered and all electrical outlets shall have approved covers. Replace cover on wall outlet in rear room near exit and on floor in SW file room. |