Case: T06FR01437

Parcel: 128010420


Addresses:

1120 S WILMOT RD


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T06FR01437

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
03/20/2006 VIOL - MEANS OF EGRESS Violation · TFC 1003.6 - the path of egress travel shall not be interrupted by any building component other than the means of egress component. Obstructions shall not be placed in the required width of a means of egress. There shall not be screen doors in front of exit doors; there shall be a clear path to all required exits including from the VIP room.
03/20/2006 VIOL - MEANS OF EGRESS Violation · TFC 1004.3 - every space or room used as an assembly occupancy shall have the occupant load posted in a conspicuous place.
03/20/2006 VIOL - MEANS OF EGRESS Violation · TFC 1008.1 - means of egress doors shall be readily distinguishable such that they are easily recognizable as doors; shall not be concealed by curtains, drapes, decorations, or similar materials. The decorations shall be removed from the door in the VIP room.
03/20/2006 VIOL - MEANS OF EGRESS Violation · TFC 1008.1.8.4 - manually operated flush bolts or surface bolts are not permitted. There are several doors that have them and shall be removed.
03/20/2006 VIOL - MEANS OF EGRESS Violation · TFC 1008.1.9 - each door in a means of egress from an occupancy of Group A having an occupant load of 100 or more shall have panic or fire exit hardware.
03/20/2006 VIOL - MEANS OF EGRESS Violation · TFC 1011.1 - exits and exit access doors shall be marked by an approved illuminated exit sign. A sign is required in the VIP room