Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR01437
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | · TFC 605.3 - a working space of not less than 30"Wx36"Dx78"H shall be provided in front of electrical service equipment. This applies to all breaker panels and service disconnects inside and outside the building. | |
03/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | · TFC 605.4 - multiplug adapters shall be prohibited. There are several throughout the building. A fused plug strip is approved when plugged directly into a permanent wall receptacle. | |
03/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | · TFC 605.5 - extension cords shall not be used as a substitute for permanent wiring, shall not be affixed to structures, extend through walls, ceilings or floors or under doors or floor coverings. Currently there are numerous extension cords throughout the entire building and outside on the porches. | |
03/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | · TFC 605.6 - open junction boxes and open-wiring splices shall be prohibited. Currently there is a junction box and light fixture that needs a cover in the kitchen area, a box in the ceiling of the VIP room, the breaker panel on the back porch needs a cover, the timer box on the back porch needs a cover, splices in wires at the breaker panel next to the bar. | |
03/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | · TFC 610 - A Type I hood shall be installed at or above all commercial cooking appliances that produce grease vapors and shall comply with the requirements of the International Mechanical Code. The kitchen equipment shall not be used until the hood system has been permitted and installed. |