Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 07/19/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Approved |
|
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
605.5 - extension cords shall not be used as a substitute for permanent wiring - various locations throughout; kitchen, main dining area above decorative ceiling, to fans/lights in presentation room, in club 1922 |
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
615.3 - A working space of not less than 30"W x 36"D x 78"H shall be provided in front of electrical service equipment - various locations throughout building |
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
605.6 - Approved covers shall be provided for switch and electrical outlet covers. - in employees room, in presentation room, in kitchen and food prep areas, DJ room |
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
605.1 - Identified electrical hazards shall be abated - wall receptacles n kitchen show severe burn marks - need to be serviced or replaced, a GFCI may be required for the outlet above the sink in the food prep area. |
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
605.4 - Multiplug adapters shall be prohibited - under eaves on back porch |