Case: T06FR01431

Parcel: 134234110


Addresses:

6310 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
07/19/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
05/23/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 - extension cords shall not be used as a substitute for permanent wiring - various locations throughout; kitchen, main dining area above decorative ceiling, to fans/lights in presentation room, in club 1922
05/23/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 615.3 - A working space of not less than 30"W x 36"D x 78"H shall be provided in front of electrical service equipment - various locations throughout building
05/23/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 605.6 - Approved covers shall be provided for switch and electrical outlet covers. - in employees room, in presentation room, in kitchen and food prep areas, DJ room
05/23/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 605.1 - Identified electrical hazards shall be abated - wall receptacles n kitchen show severe burn marks - need to be serviced or replaced, a GFCI may be required for the outlet above the sink in the food prep area.
05/23/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 605.4 - Multiplug adapters shall be prohibited - under eaves on back porch