Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR01431
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
05/23/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5 - extension cords shall not be used as a substitute for permanent wiring - various locations throughout; kitchen, main dining area above decorative ceiling, to fans/lights in presentation room, in club 1922 | |
05/23/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 615.3 - A working space of not less than 30"W x 36"D x 78"H shall be provided in front of electrical service equipment - various locations throughout building | |
05/23/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 - Approved covers shall be provided for switch and electrical outlet covers. - in employees room, in presentation room, in kitchen and food prep areas, DJ room | |
05/23/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.1 - Identified electrical hazards shall be abated - wall receptacles n kitchen show severe burn marks - need to be serviced or replaced, a GFCI may be required for the outlet above the sink in the food prep area. | |
05/23/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.4 - Multiplug adapters shall be prohibited - under eaves on back porch |