Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 07/19/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Approved |
|
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
605.5 - extension cords shall not be used as a substitute for permanent wiring - various locations throughout; kitchen, main dining area above decorative ceiling, to fans/lights in presentation room, in club 1922 |
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
615.3 - A working space of not less than 30"W x 36"D x 78"H shall be provided in front of electrical service equipment - various locations throughout building |
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
605.6 - Approved covers shall be provided for switch and electrical outlet covers. - in employees room, in presentation room, in kitchen and food prep areas, DJ room |
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
605.1 - Identified electrical hazards shall be abated - wall receptacles n kitchen show severe burn marks - need to be serviced or replaced, a GFCI may be required for the outlet above the sink in the food prep area. |
| 05/23/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
605.4 - Multiplug adapters shall be prohibited - under eaves on back porch |