Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 05/22/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cord going up into ceiling: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. *** Remove the cord going up into the ceiling. |
|
| 05/22/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ***Clear area in front of electrical panel in an approved manner. [office and main panel in back room.] |