Case: T06FR01401

Parcel: 13701007Q


Addresses:

5670 S NOGALES HY


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR01401

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2006 INSP - FULL Approved final inspection
05/17/2006 INSP - FULL Correction Required 2003 IFC-extension cords remove and replace with power surge protector.
2003 IFC-903.4 The automatic fire extinguisher was tested, the tag was not installed to show proof of service. you shall show proof of service.
2003 IFC-605.5.2 Storage up against the electrical panel. you shall have 30" width and 36" depth from the panel.
2003 IFC-901 Fire department connections south wall, remove storage from the fire department connections.
2003 IFC-1011.2 Exit lights and emergency back up lights. shall be in good working condition at all times.