Case: T06FR01358

Parcel: 12106001B


Addresses:

5851 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR01358

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2006 VIOL - FIRE PROTECTION SYSTEMS Approved
05/15/2006 VIOL - FIRE PROTECTION SYSTEMS Violation 1. Fire Extinguishers out of date:
2. Sprinklers- painted:

TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
***1. Extinguishers shall be inspected and tagged in accordance with this code.
***2. Since painting sprinkler heads invalidates the UL listing [changed the original condition of the head] ALL heads previously and currently painted shall be replaced.
Proof of the abovementioned work shall be given to the fire marshal.


Re-inspection scheduled for 6/6/06. Thank you.