Case: T06FR01356

Parcel: 141153530


Addresses:

8080 S HOUGHTON RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR01356

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2006 VIOL - FIRE PROTECTION SYSTEMS Approved ALL OK. WAITING FOR LOCK BOX.
05/15/2006 VIOL - FIRE PROTECTION SYSTEMS Violation 1). Room where riser is located must have sign indicating Fire Sprinkler Riser. IFC 901.6
2). On sprinkler riser, tamper alarm box is falling off and is detached. Electrical junction box must be attached. IFC 901.6 and IFC. 605.1
3). TFD recommends no storage in outdoor area of electrical transformers, emergency generator and refrigeration equipment.
30 inches clearance shall be maintained around all electrical equipment. IFC 605.3
4). TFD recommends placing red cage around sprinkler head on compactor heard. Please consult contractor